Sample the loop
Every 50–100 days, then after any make-up addition or vacuum fill.
>
Skip to contentA product page says what a model does; a commissioning sheet asks what the loop must hold. Sealing is where loops fail: a compression fitting cold-flowing under sustained clamp load, a seal face abraded by 5 µm particulate. Neither appears on a heat-rejection curve.
protection rating · commissioning staging · strainer rating
Which chemistry band the loop must hold.
Principle, siting and alarm thresholds.
Compound, braid class, termination, margin.
Interface plane, gap, assembly pressure.
Order of operations, and the cleanliness gate.
Five model codes per guide, one PDF each.
| Parameter | DI technology loop | Glycol or facility water | Read by |
|---|---|---|---|
| pH | 8.0–9.5 | 7.0–9.0 | EMS-CF-WQ-PH |
| EC | 0.2–20 µS/cm | 50–300 µS/cm | EMS-CF-WQ-C |
| Chloride | <5 ppm | <50 ppm | Lab panel |
| Hardness | <20 ppm | <50 ppm | Lab panel |
| Suspended solids | <3 ppm | <3 ppm | EMS-CF-WQ-PC |
| Turbidity | <1 NTU | <1 NTU | EMS-CF-WQ-NTU |
| Bacteria | <100 CFU/mL | <1 000 CFU/mL | Lab panel |
| Leak setpoint | 150 µA, 20 s | 150 µA, 20 s | EMS-LD-C16 |
| Product line | Criterion | Threshold | Figure type |
|---|---|---|---|
| Hose and fittings | burst margin | ≥3× maximum allowable | ratio |
| Thermal materials | impedance at pressure | 0.02 °C·in²/W at 30 psi | condition |
| Coolant filtration | absolute rating, finest channel | 7–10× smaller · 2× full flow · 10× side-stream | protection |
| Coolant filtration | unit-inlet guard | 500 µm class | strainer rating |
| Leak detection | zones per controller | 32 virtual zones | capacity |
| Commissioning | cleanliness class before fill | zero particles ≥50 µm | acceptance limit |
| Commissioning | flush sequence | 100 → 50 → 25 µm | staging |
Every 50–100 days, then after any make-up addition or vacuum fill.
Monthly where nuisance alarms are expensive, annually otherwise.
At 35 psid, not on a date, inside the 60 psid collapse limit.
1.4 mL per ASTM D1121; the annual check on the inhibitor package.
A wet-washed sensing cable needs 6–48 hours before it goes back down.
A date starts the panel, not a fault.
| Rule | Without the label | With the label |
|---|---|---|
| Loop type travels with the number | 0.2–20 µS/cm at pH 8.0–9.5 | 50–300 µS/cm at pH 7.0–9.0 |
| A micron figure says which one | 5 µm | protection rating · commissioning staging · strainer rating |
Supplied: filter elements and side-stream skids, water-quality instruments, leak-detection cable and controllers, hose and fittings, thermal interface materials, telemetry kits, fill-and-flush equipment. Not supplied: coolant distribution units, and cold plates.
30–150 kPa technology-cooling pressure drop · 5 s make-up alarm
| Line | Status |
|---|---|
| Filter elements and side-stream skids | Supplied |
| Water-quality instruments | Supplied |
| Leak-detection cable and controllers | Supplied |
| Hose, fittings, thermal materials | Supplied |
| Telemetry kits, fill-and-flush equipment | Supplied |
| Coolant distribution units | Not supplied |
| Cold plates | Not supplied |
Leave your work email and the model code. One datasheet per model, with position resolution and locating repeatability stated as separate rows.