>
Project files · no names

Five files, written at industry level

Each file carries the same four elements, in the same order.

No customer name, no logo and no brand mark appears here or in any file.

Ask for the specification sheet

An under-floor cable run secured with clips, seen from above
Under-floor sensing run
01 / How to read a file

The key, and the rule

Situation · requirement · supplied · outcome

No customer name

Racks are counted, halls by area, operators by segment.

No name appears in a file, caption or image.

No logo, no brand mark

No logo rail, no client strip and no partner mark is published here.

The rule binds images and alt text.

Two numbers per file

One from the specification, one from the outcome.

Five files, the same order.

Anonymised reference files — inspection record, commissioning log, acceptance criteria — are available against a model code and loop description.

02 / File 01 · colocation

Phased retrofit with tenants live

Sensing cable clipped along an under-floor route at regular spacing, with a leader connection in the foreground
Situationa 1,100 m² colocation hall converted to liquid cooling in phases, tenants live throughout
Requirementlocate a first drip inside a locked tenant rack, without a nuisance alarm
Supplied190 m of EMS-LD-R500 rope on two controller channels · EMS-LD-C8 controllers · clips at roughly 1 m spacing
Outcomefirst leak located at 3.4 m along channel 2 on day 11, at 0.1 m position resolution against ±1.08 m locating repeatability at 190 m of cable · 2 nuisance alarms in 90 days, both from floor-sealing chemical
03 / File 02 · AI training hall

Filtration at 132 kW per rack

Situationan AI training hall moving to 132 kW racks on a 4,800 L secondary loop, with commissioning debris reaching 100–400 µm microchannels
Requirementhold suspended solids below 5 µm at the cold plate, and know when a cartridge is spent
SuppliedEMS-CF-S08 side-stream skid · EMS-CF-F1-10 and EMS-CF-F5-20 cartridges, coarse to fine · EMS-CF-FP-DP transmitters
Outcomefull loop turnover every 10 hours · first cartridge changed at 35 psid (2.4 bar), inside the 60 psid (4.1 bar) element maximum · under half the terminal value at day 90
Differential pressure over 90 days 60 PSID 35 PSID DAY 0 DAY 90
Jumper bundles on a rack manifold with quick-disconnect couplings

Jumper bundle on a manifold

04 / File 03 · HPC

Repeated intervention in a 40 mm gap

Situationa mixed-generation HPC hall where nodes were swapped repeatedly and clamped jumpers weeped at the clamp band after a year
Requirementa rack-interior jumper that survives repeated intervention in a 40 mm gap
SuppliedEMS-HP-J2-06-QD quick-disconnect bundles: EPDM −6 at 9.5–10.3 mm inside diameter, 37 mm bend radius, 4.0× burst margin, no clamp
Outcome640 bundles over 14 months · clamp-band weeps in the following 12 months: 0 · 3 sleeve seizures, all after a coupling mated under pressure
A 40 mm rack gap at a 37 mm bend radius 40 MM R 37 MM
Rack gap and routed radius
05 / File 04 · edge and telecom

Nobody on site inside 90 minutes

An outdoor cabinet with a point probe above a drip tray
Situation46 unmanned outdoor cabinets on glycol loops, with no technician inside 90 minutes
Requirementan alarm that reaches the building management system over Modbus RTU with the zone named, no trip on condensation
SuppliedEMS-LD-P2 point probes set 3 mm above the cabinet floor · EMS-LD-C2 zone controllers · leak setpoint 150 µA for 20 s, contamination setpoint 50 µA for 120 s
Outcome11 alarms in 12 months, 9 confirmed coolant and 2 condensation that did not repeat · scheduled site visits fell from a monthly round to 3 in the year
06 / File 05 · burn-in floor

Grease pumping out of a 0.05 mm bond line

Situationa burn-in floor replacing thermal grease on accelerator modules every quarter because the paste pumped out of a 0.05 mm bond line
Requirementhold interface resistance across thermal cycling at the same pressure
SuppliedEMS-TM-PC85 phase-change sheet: 45–55 °C transition, 0.20–1.0 mm, ≤0.0078 °C·cm²/W by ASTM D5470, UL 94 V-0
Outcomerework interval moved from 90 days to beyond 12 months on 220 modules · joint impedance within 0.002 °C·cm²/W of the as-built value after 500 cycles
Impedance against cycle count, grease and phase-change 0 500 GREASE PC85 IMPEDANCE
Impedance against cycles
Specification request

Ask for the specification sheet

Leave your work email and the model code. One datasheet per model, with position resolution and locating repeatability stated as separate rows.

  • A specification table of at least ten rows per product family, and a downloadable PDF for every model listed.
  • Seal-life data where it decides the choice: permeation rate, compression set and fluid compatibility.
  • One working day for a reply, from an engineer rather than a catalogue autoresponder.
Reply within one working day