EMS-Trade
Cooling
Loop consumables

Document ECT-01 · REV C · ISSUED 2026-09 Six lines · 48 sheets

Raised floor void: the locating sensing rope run along a chilled water pipe between the pedestals, water beading on an insulated joint above it
Plate 01 · Leak detection · line 02 of six

Leak detection for the liquid cooling loop

Locating rope, point sensors and the controller that report a wet joint to the BMS.

Request the specification file One business day, with the file attached

Locating resolution 0.1 mDetection length 500 m per channelAlarm within 30 sChannels 4 · 8 · 16

01

The leak is found below the floor. The round is above it.

Section 01 · the floor void

The loop runs under the raised floor, through joints nobody lifts a tile to inspect. A weep there reaches no ceiling sensor and shows on no walk-round. It reaches the slab, spreads sideways, and the first visible sign is a wet tile rows away.

Three devices close that gap: a locating rope for distance, point sensors for a drip tray, and a controller that turns either one into an address on the building management system.

Scope of this line: the loop and its sensing. We do not supply the CDU, and we do not supply the cold plate.

0.1 m Locating resolution The position along the run, not a zone number
500 m Detection length Per channel, rope run or point sensor
30 s Alarm response Including the locating calculation
4 · 8 · 16 Channels per controller One rope run or one point sensor each
Cold aisle between two rows of black server cabinets with yellow cable trays running overhead, a white wall and a glass screen at the far end
FIG 01

Above the floor: the aisle a round walks, trays overhead, and a slab that hides everything under it.

Raised floor void from the side: the sensing rope run along an insulated pipe on the slab, a drip hanging from a joint and a dark patch spreading on the concrete
FIG 02

Below it: the rope is laid where the coolant arrives, not where the round passes. On the slab, beside the pipe.

02

A rope for distance, a point sensor for one drip tray

Section 02 · sensing

Two braided electrodes under a woven jacket. Water changes the impedance between them, and the controller times the round trip to that change: a position along the run, to 0.1 m.

A point sensor does the same work in one place: a drip tray, a valve gland, a pump seal. It is a dry contact device, so a channel takes either without a change at the panel.

Detection length
up to 500 m per channel of rope, or one point sensor
Locating resolution
0.1 m along the run
Alarm response
30 s, including the locating calculation
Against false alarms
a dust weave and an anti-condensation design, against dust, condensation and metal particles
Where the rope goes
raised floor voids, trenches, ceiling plenums, pipe runs
Macro of the sensing rope: two braided electrodes under a woven jacket, water beading at one point of the weave
PL 01

Two electrodes, one jacket. Water between them is the measurement.

Coiled yellow twisted-pair sensing rope with a black threaded end connector at each end, on a white ground
PL 02

Cut to the run, both ends terminated before the rope leaves the reel.

Beige braided sensing rope in a loop with a black in-line detection module and a short lead ending in a white plug
PL 03

Sensing run with an in-line module: the same rope, one addressable place.

Two point sensors lying in a steel drip tray under a manifold, each on a short lead, the tray floor dark where water has pooled
FIG 03

A drip tray under a manifold, where a gland drips into steel rather than onto the slab.

Read next · Locating sensing rope · Point sensors

03

One controller carries the channels and the reporting

Section 03 · controller and accessories

A wall unit with 4, 8 or 16 channel terminals. Each channel takes one rope run or one point sensor, and carries its own address.

It reports over Modbus RTU, a dry contact relay or a 4–20 mA loop, whichever the site already runs. A wireless gateway carries that report where no cable can be run.

Channels
4, 8 or 16 per controller
Outputs
Modbus RTU, dry contact relay, 4–20 mA loop
Lead cable
multi-core lead and flat ribbon, cut to the run length
Accessories
end terminations, extension leads, terminal resistors
Documentation
CE and RoHS on the controller, EN 10204 3.1 certificates on the metal parts
Sixteen channel controller on a wall: green terminal pairs along the bottom edge, a column of channel LEDs and a hinged cover on a grey enclosure
FIG 04

Sixteen channels in one enclosure: a pair of terminals per rope run or point sensor.

Black finned gateway with four antennas, a green RS485 screw terminal, an RJ45 port and a DC power socket on the front panel
PL 04

For sites with no spare pair to the BMS: RS485 in, wireless out.

Where a run ends short of the panel, a lead cable closes the gap. Accessories are cut and terminated to the run.

Coiled flat yellow lead cable with red and black tail wires ending in crimped ferrules, on a white ground
PL 05

Lead cable, ferrules fitted.

Coiled braided sensing rope with an in-line black sensor module and a white signal connector, on a white ground
PL 06

Termination lead for the end of a run.

Read next · Controllers · Accessories

04

One channel is one pair of terminals

Section 04 · wiring

The rope or the point sensor lands on a pair of terminals. The shield goes to the same earth as the panel, and the far end of a run closes at an end termination. Three paths leave the controller.

Wiring: rope runs and a point sensor into the controller, and three paths out to the BMS Channel 1 takes rope run 01, channel 2 takes rope run 02, channel 3 takes a point sensor. Modbus RTU, a dry contact relay and a 4 to 20 mA loop leave the controller. raised floor line Rope run 01 Rope run 02 Point sensor 03 01 02 Controller 4, 8 or 16 channels CH 1 CH 2 CH 3 Modbus RTU dry contact 4–20 mA 04 BMS or DCIM

Key

  1. 01Rope channel: one pair of terminals, one run, up to 500 m.
  2. 02Point sensor on the same pair of terminals.
  3. 03End termination closes the far end of a run.
  4. 04The report leaves over one of three paths.
FIG 05

Sensing on the left, reporting on the right. One pair of terminals per channel.

Modbus RTU: two wires on RS485, address set at the panel.

Dry contact: a volt-free relay for a local alarm or a PLC.

4–20 mA: an analogue loop for a current input.

Controller terminals in close view: a pair of wires landed under each screw, the pairs numbered along the strip and a shield wire on the earth bar
FIG 06

Terminals landed and numbered, one pair per channel.

Two cooling towers on a roof deck with galvanised hand rails, access ladders and black supply pipework
FIG 07

The loop does not stop at the hall: plant decks carry the same joints.

Rooftop bank of condenser units with insulated pipework and blue valves running along the deck
FIG 08

One channel can cover the deck and report its position.

Read next · Telemetry instruments · Design guides

05

Choosing a channel count

Section 05 · selection

Count the areas you want addressed separately, not the metres of pipe. Two aisles and a plant room are three areas, and every channel covers up to 500 m of rope or one point sensor.

Two aisles and a plant room: three areas on a 4 channel controller.

Channel selection · one controller per area count
Channels Areas addressed Detection length Where it fits
4 channels up to 4 areas 500 m per channel One hall, or a hall with its own plant room
8 channels up to 8 areas 500 m per channel Two halls, or one hall with separate aisles
16 channels up to 16 areas 500 m per channel Multi-hall sites and phased fit-out

Two aisles on one channel report one wet tile between them. Two aisles on two channels name which one.

Monitored areas · server halls · aisles · CDU connections · plant rooms · battery rooms · UPS rooms · chiller supply and return

A cut length of beige sensing rope on a bench, one end stripped back to two electrodes and the other closed with a black end cap
FIG 09

Rope is cut to the area: the run length follows the count of channels you chose.

Coiled blue twisted-pair sensing cable with black end connectors, on a white ground
PL 07

One channel, one long area: 500 m of detection.

Coiled white twisted-pair sensing cable with two black cylindrical connectors, on a white ground
PL 08

One channel, one short area: cable cut at the bench.

Read next · Design guides · Industries

DOCUMENT REQUEST

Request the specification file

Four documents are held for this line. One request returns them attached, next business day.

  • Specification sheet rope, sensors, controller
  • EN 10204 3.1 material certificates metal parts
  • Test report on request
  • Outline drawings controller and end terminations
The only promise on this page

One business day, with the file attached.

No other commitment is made on this sheet. Price, stock and lead time are not promised here.

If the form cannot send, this address takes the request instead: sales@ems-cool.com

Beige braided sensing rope looped on a white ground with a black detector module at one end and a white tail wire at the other
PL 09

Sensing rope with its detector module, terminated before packing.

Coiled yellow braided sensing rope with two black threaded connectors, on a white ground
PL 10

Rope set with both ends terminated.