>
Commissioning

Fill, flush and filtration for liquid cooling loops

A loop is cleanest the day it leaves the factory. Most particulate a filter catches enters on commissioning day.

Piping cleanliness class CCC= C(C13/D9/E-N00)

0 at or above 50 µm · ≤5 000 at 15–25 µm · ≤350 at 25–50 µm, per 1 000 cm².

Downtime 140–540k USD/h

Cost of a loop out of service.

No coolant distribution units, no cold plates.

A grey coolant fill cart with a blower unit on a plantroom floor, its hose run leaving the frame before it reaches a manifold

Fill cart landed on an open rack manifold

01 / Deployment order

Four machines, in the order a loop meets them

Deployment order of the four commissioning machines on one loop outline 01020304 Fill Flush Filtration Charge C120 · C200 · C500 FL75 · FL340 · FL1300 FS20 · FS60 · FS150 PG15 to PG55 120 / 200 / 500 L 100 to 25 µm commissioning staging 5–15 % side-stream 25 % PG · −10.1 °C 8 racks · over 60 L/min at or above operating velocity turnover every 6–12 h ASTM D1384 commissioning staging protection rating
Deployment order · four stages, one loop outline
02 / Contamination routes

Three ways a clean loop gets dirty

Water

Municipal water carries particles a loop does not allow.

Filters

A wet filter retains contaminants, so replacement beats cleaning.

Compressed air

Drying air can dispense oil onto filter surfaces.

A thermal fill station carries an inline filter in its supply line.

03 / Commissioning staging

The flush is a procedure with a stop condition

Commissioning staging ladder from 100 to 25 µm against the particle-size limit commissioning staging — 100 µm commissioning staging — 50 µm commissioning staging — 25 µm stage 01stage 02stage 03 coarsefine
Staging ladder 100µm · commissioning staging

A procedure, not the protection rating of the filter that runs afterwards.

Flush velocity operating
Design envelope 6.9bar

100 psig, 60 °C (140 °F).

04 / Flush boundary

The CDU sits outside the flush loop

Flush boundary with the coolant distribution unit bypassed flush skid loop pipework coolant distribution unit heat exchanger bypass flush boundary
Item Requirement
CDU as the flush pump Avoided · contaminants reach its heat exchanger
Internal weld joints Ra 0.5 microinch max
Passivation ASTM A-380 · or 2 h at 60 °C, ASTM A-967
Inlet strainer at a unit 500 µm class · strainer rating, not a filtration stage
05 / Filtration duty

The flush ends; filtration does not

Side-stream fraction against circulating loop volume side-stream vessel 5–15 % of volume side-stream tapping about 10 % per hour · turnover every 6–12 hours
Placement Multiplier
Full-flow filter about 2× smaller · carries the whole flow
Side-stream filter up to 10× smaller · carries a fraction of loop flow
Protection rating · absolute, not nominal 7–10× smaller · a 50 µm passage takes a 5 µm filter

The skid range routes to filtration skids.

06 / Fluid decision

Inhibited premix, or raw glycol

Carbon-steel corrosion on one test at one concentration. Acceptance basis ASTM D1384, target below 0.5 mils penetration per year for all system metals.
Fluid Corrosion
Inhibited propylene glycol, 40 % 0.01 mpy
Raw uninhibited propylene glycol, 40 % 23.65 mpy
Difference 2 365×
Reserve alkalinity minimum, ASTM D1121 15.0 mL
Automotive antifreeze Not acceptable in any fluid system

25 % premix freezes at −10.1 °C. Viscosity runs 1.68 mPa·s at 15 % to 8.20 mPa·s at 55 %, at 20 °C.

07 / Model index

Eighteen codes, one document each

Fill carts, flush skids, filtration skids and coolants, in deployment order. The full multi-row specification for each code is in its PDF.
Model Tank or flow Sheet
EMS-FF-C120120 LPDF
EMS-FF-C200200 LPDF
EMS-FF-C500500 LPDF
EMS-FF-FL7575 L/minPDF
EMS-FF-FL340340 L/minPDF
EMS-FF-FL13001 300 L/minPDF
EMS-FF-FS2020 L/minPDF
EMS-FF-FS6060 L/minPDF
EMS-FF-FS150150 L/minPDF
EMS-CL-PG1515 % · −5 °CPDF
EMS-CL-PG2020 % · −7.2 °CPDF
EMS-CL-PG2525 % · −10.1 °CPDF
EMS-CL-PG3030 % · −13.3 °CPDF
EMS-CL-PG4040 % · −22.2 °CPDF
EMS-CL-PG5050 % · −35.0 °CPDF
EMS-CL-PG5555 % · −43.3 °CPDF
EMS-CL-PGCconcentratePDF
EMS-CL-DIW0 %PDF
Specification request

Ask for the specification sheet

Leave your work email and the model code. Send the loop volume, the target cleanliness class and the fluid with the code where the sizing is the question.

  • A specification table of at least ten rows per code, and a PDF for every model above.
  • Seal-life data where it decides the choice: permeation rate, compression set and fluid compatibility.
  • One working day for a reply, with the datasheet, the procedure sheet and the lead time.
Reply within one working day