EMS-Trade
Cooling
Loop consumables

Document ECT-01 · REV C · ISSUED 2026-09 Six lines · 48 sheets

Transmitter photographed against a black ground: a blue-capped white housing on a stainless process connection
Flanged in-line meter with a blue-capped transmitter head on a stainless body, photographed on a white ground
Black finned gateway with four antennas, a green screw terminal block, a LAN port and a DC power socket along its front edge
A filter trolley on a wheeled frame: two grey cylindrical housings with flanged tops, blue-handled ball valves, a pump below and a round gauge on the outlet
Sheet 06-3 · Telemetry · fluid quality monitoring

Fluid quality monitoring for the liquid cooling loop

Conductivity, pH and level are read at the reservoir, and each one is bought on a different criterion. This sheet puts the criteria in the order they actually decide, then the three classes side by side and the limits they are held to.

Request the specification file One business day, with the file attached

Cleanliness ISO 4406 17/15/12 Filtration 1 µm absolute Filter change-out 0.5–0.7 bar

01

The criteria, in the order they decide the choice

Section 01 · criteria · ranked by what it costs to get wrong

A criteria list sorted by the number of parameters a datasheet carries is a list of features. The list below is sorted by what it costs when the criterion is missed: the three at the top each end a loop, and the ones below them only cost money.

It is also the order the questions arrive in. What is the loop being protected from, what is in it, and how clean is it? The range and the output are decided by those three, not the other way round.

Selection criteria · what settles each one, and why it ranks where it does
Criterion What settles it Why it ranks here
What the loop is protected from Corrosion, elastomer attack, or a reservoir drawn down It decides which of the three readings is worth buying at all
What is in the loop Water, or water with glycol Decides the wetted material and the cell constant before any range
How clean it is ISO 4406 17/15/12 before first power-on A reading taken on a dirty loop is a reading of the dirt
Filtration rating 1 µm absolute; the range runs 0.05–100 µm The probe gap and the particles are the same order of size
Conductivity range Recorded in µS/cm Sets the cell constant; the wrong one reads off scale at both ends
pH range The loop's own working band Sets the electrode and the reference, which is where pH goes wrong
Level range Reservoir geometry and the pump inlet height Sets the stem length; a level sensor is a mechanical fit first
Differential pressure 0.5–0.7 bar at filter change-out The change-out signal the water reading is judged against
Output 4–20 mA, or Modbus RTU Decides whether the reading is logged or only seen
Wetted material Stainless, matched to the loop's own parts A probe that is not the loop's alloy is a corrosion cell
A conductivity probe screwed into a flow-through cell on a bench, the cell body drilled with a small bore and the cable gland at the top
FIG 01

A flow-through cell keeps the probe wet and the reading comparable.

A pH electrode standing in a sample pot on a bench with its reference junction below the liquid line and a buffer bottle beside the pot
FIG 02

The junction has to stay wet. An electrode stored dry reads a different loop.

A level sensor with a long stem laid on a bench beside a section of reservoir wall, the stem reaching from the top plate towards the outlet
FIG 03

The stem is measured to the pump inlet, not to the bottom of the tank.

Read next · Water quality · Design guides · Telemetry

02

The three classes, in one frame

Section 02 · comparison · what separates one class from the next

Three instruments side by side on a bench: a conductivity probe in its cell, a pH electrode on a stand, and a level sensor with a long stem
FIG 04

Three classes, one bench. What separates them is where the sensing surface is.

A transmitter mounted on the top plate of a stainless reservoir with its probe reaching down into the fluid and a sight glass beside it
FIG 05

Mounted at the reservoir, because that is where the fluid is quiet and the level is known.

A flow-through cell cut open on a bench with the two electrodes visible inside the bore and a small filter screen at the inlet
FIG 06

The cell sets the constant. Two electrodes and a fixed bore decide what a µS/cm means here.

A sample pot drawn from a loop drain point with the probe lowered into it, a second pot of clear fluid beside it for comparison
FIG 07

A manual sample is the reference the inline reading is checked against, once a quarter.

Read next · Coolant filtration · Commissioning · FAQ

03

The limits the instruments are held to

Section 03 · limits · past these, the reading is not usable

Media temperature
−40 to +99 °C on the wetted parts and the seals
Ambient, edge site
−20 to +55 °C, which is what decides the housing rather than the probe
Loop pressure
1.38 MPa working, with a burst pressure of at least 5.5 MPa
Housing design pressure
at least 1.0 MPa on the filter body the probe sits beside
Cleanliness
ISO 4406 17/15/12 before first power-on, filtration to 1 µm absolute
Element change-out
at 0.5–0.7 bar differential; the calendar does not decide it
Alarm response
within 30 s of the reading leaving the band
Loop life
5–10 years, with the coolant aged inside the same loop across generations of equipment
A probe and its cable gland on a hot insulated pipe with the insulation drawn back, heat haze absent, the gland sealed against the line
FIG 08

The hot end of the range is a seal problem before it is an electronics problem.

An outdoor cabinet on a telecom site with a probe line entering through a gland and frost on the ground beside the plinth
FIG 09

At an unmanned site the ambient range decides the housing, and the housing decides the year.

Read next · Edge & telecom · Notes on ISO 4406 · Capabilities

04

The mistakes that cost the most, and what each one costs

Section 04 · misuse · one line each

  • Reading conductivity straight after a top-up. The make-up water reads low and hides the trend it was installed to follow.
  • Calibrating pH against a buffer that has stood open. The loop is then dosed against a number that moved before the dosing did.
  • Fitting the level sensor to the tank wall instead of to the pump inlet. The pump cavitates while the tank still shows level.
  • Judging the element by the supply pressure instead of the differential. The supply pressure moves with everything else on the loop.
  • Changing the element on a calendar. The differential decides the change-out, and a loaded element is the only signal that matters.
  • Comparing one site's µS/cm against another's. The reading belongs to the loop it was taken on, and so does the baseline.

Every one of these is a reading that was taken, logged, and then believed for the wrong reason.

A make-up line entering a reservoir through a float valve with a sample pot beside it, the fluid in the pot markedly clearer than in the tank
FIG 10

Make-up water dilutes the reading as well as the coolant.

A probe pulled from its cell and laid on a bench beside the cell, its sensing surface dry and filmed, a brush and a rinse bottle beside it
FIG 11

A probe left dry between fills reads the next loop as if it were a different fluid.

Read next · Design guides · Notes · FAQ

05

Documents and packing, per shipment

Section 05 · documents · the paperwork is part of the purchase

Certificates
EN 10204 3.1 on the wetted metal parts, per batch
Calibration
recorded against a reference before the certificate is signed, per batch
Drawings
outline drawing per part, with the mounting thread and the stem length marked
Declaration
CE marking on the electronics, RoHS and REACH on the materials, ISO 9001 behind the batch record
Commercial
packing list, invoice, certificate of origin in English; ISPM 15 timber on crates
Lead time
samples 7–10 days, production 25–35 days, FOB Shenzhen
An open document folder on a bench with a material certificate on one side and a calibration record on the other, a probe standing beside it
FIG 12

The calibration record and the certificate are signed together, not on separate days.

An open carton with two probes in shaped foam and a bottle of storage fluid standing beside them, the lid leaning against the carton
FIG 13

Probes ship wet, in their storage fluid, for the reason the mistake above describes.

Read next · Quality & inspection · Legal · Contact

Document request

Four documents are held for this sheet. Tick the ones you need.

Tick a document, name the coolant and the range you are fitting, and the file comes back attached.

The only promise on this page

One business day, with the file attached.

Nothing else on this sheet is promised. Price, stock and lead time are not promised here.

If the form cannot send, the address below takes it instead: sales@ems-cool.com. A request is never accepted and then dropped.
A reservoir drawn down for a fill, with a probe lowered into the fluid from the top plate and a sample pot on the floor beside the drain valve
FIG 14

The reading is taken with the loop at working temperature, not on a cold fill.

A tag on a sample pot with the loop, the date and the reading written on it, a second tagged pot beside it from an earlier sample
FIG 15

Two tagged pots are a baseline. One number on a screen is not.