EMS-Trade
Cooling
Loop consumables

Document ECT-01 · REV C · ISSUED 2026-09 Six lines · 48 sheets

Sheet 20 · Line 01 of six · selection

Locating sensing rope

One channel of rope reports a position along the run, not a zone. The controller times the change in impedance between two braided electrodes and returns the distance to the wet point.

One business day, with the file attached
A locating sensing rope laid along a chilled water pipe in a raised floor void, the woven jacket running between two pipe supports
PL 01 ·

Rope is laid where the coolant arrives, not where the round walks. On the slab, beside the pipe.

01

Choose the run first, the rope second

Section 01 · selection criteria

A rope is chosen by the run it has to cover, not by the diameter of the cable. The rows below are in the order a loop is actually specified: how far one channel reaches, what has to come back from it, and what the air around it is like.

Rope is cut to the run and terminated at both ends before it leaves the reel. A site that cuts and re-terminates on the slab changes the length the controller was calibrated to, and every position reported afterwards reads short by what was removed.

Selection criteria · in the order the loop is specified
Criterion What you decide Figure If it is specified wrong
Length of the run One channel of rope, or the run split across two 500 m per channel Past that the far end falls outside the locating calculation
What has to come back A position along the run, or only the area 0.1 m A zone sends the technician to the wrong aisle
Air around the rope Woven jacket, or plain twisted pair dust weave Dust, condensation and metal particles alarm a dry run
A gland between runs Rope with an in-line module, or two plain runs 1 addressable place Two channels spent on one drop
How many areas One controller, or a second one later 4 · 8 · 16 A shared channel names a wet tile, not which aisle
What the BMS speaks Modbus RTU, a volt-free relay, or an analogue loop 4–20 mA A protocol converter added after commissioning
A locating rope run on a slab beneath a raised floor, fixed at intervals along the pipe route and passing under a floor pedestal
PL 02 ·

The run is the unit of selection. One channel, one route, up to 500 m.

Gold braided sensing rope coiled on a white ground with a black in-line module on the lead and a white tail wire
PL 03 ·

A rope set with its module, cut and terminated before it is packed.

Macro of the woven jacket where a drop of coolant has reached the braid, the weave dark and wet at one point
PL 04 ·

Water between the two electrodes is the measurement.

Read next · Point sensors · Controllers

02

Three rope constructions, and what each one buys

Section 02 · the range

Three constructions cover the range. What separates them is visible in the jacket and in what sits between the electrodes, and each one answers a different condition in the void.

Close view of a plain twisted pair of electrodes with no outer jacket, the two conductors laid together and separated at the cut end
PL 05 ·

Twisted pair: the two electrodes are the pair, with nothing over them.

Cut end of the woven rope jacket showing two braided electrodes inside the weave, the jacket fibres splayed at the cut
PL 06 ·

Woven jacket: the dust weave over two braided electrodes.

The black in-line module on a rope run in close view, its sealed body clamped between two lengths of the woven jacket
PL 07 ·

Module: the same rope, one place on it addressable on its own.

Coiled blue twisted-pair sensing cable on a white ground, held with two white ties and closed with a black connector at each end
PL 08 ·

Cut to the run, terminated at both ends, packed on the reel.

Twisted pair
A dry trench or a cable tray, where dust is not the problem. Gives a position to 0.1 m.
Woven jacket
The standard rope. A dust weave and an anti-condensation design against dust, condensation and metal particles, over up to 500 m per channel.
Woven jacket, in-line module
A valve gland or a pump seal sitting between two long runs. Alarm within 30 s including the locating calculation.

Read next · Accessories · Design guides

03

Where the rope stops being the right device

Section 03 · boundary conditions

The figures below are limits, not ratings. The rope works up to each boundary and stops being the right device after it, so each line also says what to do instead.

One channel of rope
Up to 500 m per channel. Past it the far end is outside the locating calculation, start the next channel and give it its own address.
Position along the run
0.1 m. This is the number a technician keys into the floor plan; a zone cannot be keyed, only searched.
Time to alarm
30 s including the locating calculation. A slower path to the BMS is a longer spill at the joint.
Channels on one controller
4 · 8 · 16. Past 16 a second controller starts and the address the BMS reads changes with it.
Output the site already runs
Modbus RTU, a volt-free relay or a 4–20 mA loop. A site with no spare pair to the BMS needs the wireless route instead.
Rope is a consumable
Loops run 5–10 years. Rope is replaced with the joints it watches rather than cleaned and reused.
A rope end termination on a bench in close view, the jacket stripped back to two electrodes and closed inside a black threaded connector
FIG 01 ·

Both ends are terminated at the bench. The run length the controller is calibrated to is decided here, not on the slab.

Two rope runs meeting at a floor void boundary, each on its own lead heading away in a different direction toward a controller
FIG 02 ·

At the boundary the run is split rather than extended, and each half keeps its own address.

Read next · Controllers · Telemetry instruments

04

Specified wrong, it reports the wrong place

Section 04 · common misreading

  • Laid along the walk-round path instead of the pipe. It alarms where the technician already stands, and the wet joint stays dry.
  • One channel across two aisles. The report names a wet tile between them, and both aisles have to be opened to find it.
  • Plain twisted pair in a dusty trench. Dust and metal particles change the impedance too, so the channel alarms without water.
  • Cut and re-terminated on site. The locating calculation is calibrated to the terminated length and every position reads short.
  • A run past 500 m per channel. The far end falls outside the calculation and the last metres report as nothing at all.
  • Waiting on the rope to stop the leak. It returns a position to 0.1 m; it does not close a valve or a pump.
A rope laid down the middle of a cold aisle between cabinet rows, running where a person walks rather than along the pipework overhead
FIG 03 ·

Down the aisle: the rope covers the path the round takes, and not the pipe the coolant is in.

A rope cut on the slab with the jacket opened and the electrodes trimmed back by hand, loose strands left beside the cut
FIG 04 ·

Cut on the slab: the length the controller was calibrated to is now shorter than the run.

Read next · Design guides · FAQ

05

What travels with the reel

Section 05 · documents and packing

The reel travels with paper. None of these documents is optional on a data centre purchase order, and all of them are issued in English.

Material certificates
EN 10204 3.1 on the metal end terminations, traceable to the batch.
Compliance
CE marking and RoHS on the controller; REACH on the materials; ISO 9001 on the supplying plant.
Test report
Continuity and locating test report on the delivered lengths, on request.
Packing
Rope on a wooden reel; export crates built to ISPM 15.
Minimum
MOQ 1 carton; custom lengths from 500 m.
Lead time
Samples 7–10 days; production 25–35 days.
Terms
FOB Shenzhen, CIF or DDP, on the terms the order names.
A wooden reel of sensing rope in a packing area with the rope wound on evenly and a lead taped to the flange
FIG 05 ·

On the reel, cut to the run and terminated, with the length written on the certificate rather than the flange.

A cut-to-length bench with rope run out along a measured rule, a termination crimped at one end and a test lead clipped on
FIG 06 ·

Every delivered length is measured and continuity tested before it is wound.

Read next · Quality & inspection · Supply network

DOCUMENT REQUEST

Request the specification file

Four documents are held for this sheet. One request returns them attached, next business day.

  • Specification sheet rope, module, end terminations
  • EN 10204 3.1 material certificates metal parts
  • Locating test report on request
  • Outline drawings connector and module
The only promise on this page

One business day, with the file attached.

No other commitment is made on this sheet. Price, stock and lead time are not promised here.

If the form cannot send, this address takes the request instead: sales@ems-cool.com

Coiled white twisted-pair sensing cable on a white ground with a black threaded connector at one end and an end cap at the other
PL 09 ·

Twisted pair, both ends closed.

Coiled yellow braided sensing rope on a white ground, held with two white ties and closed with a black threaded connector at each end
PL 10 ·

The woven jacket, terminated both ends.