The hall stays live while the loop changes
Work goes on inside a hall that cannot be shut down, on a loop shared with other tenants. Everything here is written for the change that has to be made without a shutdown window.
Live bus · shared loop · contract clock · where it lands
What working live looks like in the aisle
In service the row keeps running while the branch is tied in
No hot work and no core drilling above the tiles
1 row is the unit a tenant branch can be isolated at
Every decision on this sheet starts from the same fact: the room is occupied while the work happens.
Two tenants, one return. A drip on one branch is read as a humidity trend on the other.
The wet slab is the first evidence, and it is under a floor nobody has lifted yet.
What we will put in writing for a live hall
| No | Condition | Value | Unit | Basis |
|---|---|---|---|---|
| 01 | Leak location resolutionLocating sensing rope | 0.1 | m | Under the tiles, along the pipe the fluid would follow |
| 02 | Detection length per channelLocating sensing rope | 500 | m | A whole aisle on one channel, position not zone |
| 03 | Alarm responseController to the BMS | 30 | s | Inside the window a tenant contract is written to |
| 04 | Contract downtime a yearTenant SLA 99.99% | 52.6 | min | One underfloor leak can spend it in an afternoon |
| 05 | Isolation per tenantBranch valve at the take-off | 1 | row | One tenant's branch can be shut without the row |
| 06 | Cartridge absolute ratingFilter on the branch | 1 | µm | Grades from 0.05 to 100 µm on one housing |
| 07 | Cleanliness at chargeLoop fluid | 17/15/12 | ISO 4406 | Sampled before any retrofit run is charged |
| 08 | Filter change differentialAcross the housing | 0.5–0.7 | bar | Read on two impulse tubes, not on a gauge by eye |
| 09 | Hose working pressureDASH −4 to −10 | 1.38 | MPa | About 200 psi, burst above 5.5 MPa |
| 10 | Hose temperature bandWater-based coolant | −40 to +99 | °C | The band claimed for this application |
The value column is the figure we will be held to, and every figure in it is one this loop is bought against. Where a tolerance is not published, the cell stays empty rather than carrying an estimate.
Where the two readings on a tenant branch come from
Filter loading is the first reading that moves when a branch stops delivering.
The rope follows the run the fluid would follow, past every joint on it.
The loop as a colocation retrofit is actually built
Consumables on this section
- 1 ·Suspended floor tiles · the work happens below them, in service
- 2 ·Existing chilled water pipe, lagged and left in place
- 3 ·Locating sensing rope run along the slab beside the pipe
- 4 ·Point sensor under a coil and a valve group
- 5 ·New tenant branch, isolation valve at the take-off
- 6 ·Filter and differential pressure transmitter on the branch
The three files this industry is held as
Three configurations recur in tenant halls. Each is held as a file: the loop drawing, the consumable list, the cleanliness gate and the sample that cleared it.
File A. One tenant, one branch, isolation at the take-off.
File B. One manifold per row, every branch isolatable from the aisle.
File C. The retrofit run: existing pipe untouched, new run beside it.
The standards a tenant hall is written against
How the same standards are demonstrated to a tenant
1.38 MPa working, burst above 5.5 MPa, and the record travels with the shipment.
The seal set is a line item, not an accessory: it is replaced at every break.
A retrofit shipment is packed so that nothing has to be fabricated on the slab: hose cut to length, ends terminated, seals bagged against the joint they belong to. What arrives in the aisle is what goes into the loop.
Cut and terminated before dispatch, so the aisle is never the place the length is decided.
What every one of those files consumes
SP 1–4 ·Supply-side samples: an in-line sensing run with its module in the middle of the cable rather than at the controller, a seal set replaced at every break, a body section drawing with the bore and wall called out, and the flow meter that reads one tenant branch.
What stops at the boundary of this sheet
We supply the loop: hose, couplings, seals, filtration, sensing rope and the instruments that read them. The cooling distribution unit and the cold plate are not ours to quote, and neither is the installation, the design or the commissioning of either.
In a tenant hall that boundary matters twice over: the unit you already own stays yours, and this sheet covers only what hangs off it.
The unit on the facility side stays the facility's. This sheet starts at the flange on it.
The other sheets in this set
Every sheet in this set is written in the same order: the pain, the schedule it is quoted on, the loop as it is built, the standards, and the configuration files held for it.
Four documents are held for this sheet. Tick the ones you need.
Tick a document, name the row or the tenant branch you are planning against, and the file comes back attached.
One business day, with the file attached.
Nothing else on this sheet is a commitment. Price, stock and lead time are not promised here.